Evaluation of a real-time PCR hybridization assay for rapid detection of Legionella pneumophila in hospital and environmental water samples

Clin Microbiol Infect. 2003 Jul;9(7):754-8. doi: 10.1046/j.1469-0691.2003.00666.x.

Abstract

A real-time LightCycler assay for Legionella pneumophila was evaluated with 120 water samples potentially contaminated with PCR inhibitors. Results were obtained within five hours, with a detection limit equivalent to 800 cells/L. However, 11 of 22 culture-positive samples containing < 100 CFU/L were also positive by LightCycler assay, indicating the presence of significant numbers of non-viable cells. Following extraction, amplification inhibitors remained in four culture-positive samples, but only one contained > 800 CFU/L. The assay seemed suitable for rapidly screening large sample numbers for heavy contamination with L. pneumophila, but conventional culture should continue to be used to detect low contamination levels.

MeSH terms

  • Legionella pneumophila / genetics
  • Legionella pneumophila / isolation & purification*
  • Legionnaires' Disease / diagnosis*
  • Polymerase Chain Reaction*
  • Water Microbiology*
  • Water Supply / analysis*